Effect of Expanded Unit Connection for Units to Low Frequency Oscillation in the Hydropower Plants. [J]. Advanced Engineering Sciences 40(6):14-18(2008)
Effect of Expanded Unit Connection for Units to Low Frequency Oscillation in the Hydropower Plants. [J]. Advanced Engineering Sciences 40(6):14-18(2008)DOI:
Effect of Expanded Unit Connection for Units to Low Frequency Oscillation in the Hydropower Plants
Abstract:According to two units with hydraulic coupling in hydropower plants
the effect of expanded unit connection to low frequency oscillation’s damping was studied in detail. With the mathematical model of hydraulic system which accurately reflectes each vibration mode of water flow
and the established mathematical model of expanded unit connection deduced from the five order integrative stability model of generator and the interface model between generator and electric power network
the whole state equations to describe the hydraulic、 mechanical and electrical system were derved
furthermore
the effect of expanded unit connection to low frequency oscillation’s damping and stability was analyzed with a given case. The results indicated that
for a system with two units having hydraulic coupling
low frequency oscillation’s damping was increased by the effect of expanded unit connection
and the effect to low frequency oscillation suppression was identical for larger increased damping on one unit and smaller increased damping on two units
while the hydraulic coupling had less effect to the distribution of damping.
关键词
水电站低频振荡扩大单元接线稳定性分析
Keywords
hydropower plantlow frequency oscillationexpanded unit connectionstability analysis